T200 User's Manual SECTION 2: SAFETY INSTRUCTIONS
PAGE 2-4
2.2 Safety regulations
1. The T200 controller must be disconnected from all power if repair work is to be carried out. Check that the mains
supply has been disconnected and that at least 5 minutes has passed, to allow for d.c. bus capacitors to discharge,
before removing motor and mains plugs.
2. Correct protective earthing of the equipment must be established, the user must be protected against supply voltage,
and the motor must be protected against overload in accordance with applicable national and local regulations.
3. Do not remove the plugs for the motor and mains supply while the T200 controller is connected to mains power.
Check that the mains supply has been disconnected and that the necessary time has passed before removing motor
and mains plugs.
Warning against unintended start
The installation of safety interlocks, additional control and protection devices must be done in accordance with the
relevant local safety requirements. Note that changes made through software can result in the motor starting suddenly.