Application Notes
P44x/EN AP/Hb
6
MiCOM P40 Agile P442, P444
(AP) 5-
9
Fault/Event/Disturbance Records - Available from the serial communications or on the
relay display (fault and event records only).
Distance to fault locator - Reading in km, miles or % of line length.
Four Setting Groups - Independent setting groups to cater for alternative power
system arrangements or customer specific applications.
Remote Serial Communications - To allow remote access to the relays. The following
communications protocols are supported: Courier, MODBUS, IEC 60870-5/103 and
DNP3.
Continuous Self Monitoring - Power on diagnostics and self checking routines to
provide maximum relay reliability and availability.
Circuit Breaker State Monitoring - Provides indication of any discrepancy between
circuit breaker auxiliary contacts.
Circuit Breaker Control - Opening and closing of the circuit breaker can be achieved
either locally via the user interface / opto inputs, or remotely via serial
communications.
Circuit Breaker Condition Monitoring - Provides records / alarm outputs regarding the
number of CB operations, sum of the interrupted current and the breaker operating
time.
Commissioning Test Facilities.
1.2.3 Additional Features for the P442 Relay Model
Single pole tripping and autoreclose.
Real Time Clock Synchronisation - Time synchronisation is possible from the relay
IRIG-B input. (IRIG-B must be specified as an option).
Fibre optic converter for IEC 60870-5/103 communication (optional).
Second rear port in COURIER Protocol (KBus/RS232/RS485)
16 Logic Inputs - For monitoring of the circuit breaker and other plant status.
Up to 21 Output relay contacts - For tripping, alarming, status indication and remote
control.
Communication protocols available (ordering specification): K-Bus/Courier, MODBUS,
VDEW (IEC 60870-5-103), DNP3.0, IEC 61850 + Courier, IEC 61850 + IEC 60870-5-
103) or DNP3.0 + Courier.