(TD) 2-
MEASURED OPERATING DATA
(MEASURE'T SETUP)
Default Display:
∗ Description
∗ Plant reference,
∗ U – I – Freq,
∗ P – Q,
∗ Date and Time.
Local Values: Primary/Secondary
Remote Values: Primary/Secondary
Measurement Ref: VA/VB/VC/IA/IB/IC
Measurement Mode: 0/1/2/3
Demand Interval: 1…99mn (step 1mn)
Distance Unit: Miles/Kilometres
Fault Location:
Distance
Ohms
% of Line
COMMUNICATIONS COLUMN
Courier protocol:
Protocol indicated
RP1 Address: 7 to 34 (step 1)
RP1 Inactiv timer: 1mn to 30 mn (step 1mn)
Physical link: RS485, Fibre optic
RP1 Status
RP1 Port configuration: Kbus/EIA(RS)485
RP1 comms mode:
∗ IEC 60870 FT1.2
∗ 10-Bit no parity
RP1 Baud Rate: 9600/19200/38400 bits/s
IEC 60870-5-103 protocol:
Protocol indicated
RP1 Address: 7 to 34 (step 1)
RP1 Inactiv timer: 1mn to 30 mn (step 1 mn)
Baud Rate: 9600/19200/38400 bits/s
Measurement period: 1 to 60 s (step 1 s)
CS103 blocking:
∗ Disabled,
∗ Monitor blocking,
∗ Command blocking.
RP1 Status
RP1 Port configuration: Kbus/EIA(RS)485
RP1 comms mode:
∗ IEC 60870 FT1.2
∗ 10-Bit no parity
RP1 Baud Rate: 9600/19200/38400 bits/s
Modbus protocol:
Protocol indicated
RP1 Address: 7 to 34 (step 1)
RP1 Inactiv timer: 1mn to 30 mn (step 1 mn)
Baud Rate: 9600/19200/38400 bits/s
Parity: Odd/Even/None
Physical link: RS485/Fibre optic
Date/Time Format: Enabled/Disabled
RP1 Status
RP1 Port configuration: Kbus/EIA(RS)485
RP1 comms mode:
∗ IEC60870 FT1.2
∗ 10-Bit no parity
RP1 Baud Rate: 9600/19200/38400 bits/s
DNP3.0 protocol:
Protocol indicated
RP1 Address: 7 to 34 (step 1)
RP1 Inactiv timer: 1 mn to 30 mn (step 1 mn)
Baud Rate: 9600/19200/38400 bits/s
Parity: Odd/Even/None
Measurement period: 1 to 60 s (step 1 s)
Physical link: RS485/Fibre optic
Time Synhronization: Enabled/Disabled
Date/Time Format: Enabled/Disabled
RP1 Status
RP1 Port configuration: Kbus/EIA(RS)485
RP1 comms mode:
IEC 60870 FT1.2/10-Bit no parity
RP1 Baud Rate: 9600/19200/38400 bits/s
Scale Value indicated
Message Gap: 0 to 50 ms (step 1 ms)
DNP Need Time: 1 to 30 (step 1)
DNP Application fragment size:
100 to 2048 (step 1)
DNP Application fragment timeout:
1 s to 120 s (step 1 s)
DNB SBO timeout: 1 s to 10 s (step 1 s)
DNP link timeout: 0 to 120 s (step 1 s)
Ethernet port, IEC 61850 protocol:
Protocol indicated
Protocol & Scale value indicated,
Network Interface Card (NIC) protocol:
Courier/IEC
60870-5-103/Modbus/DNP3.0
NIC MAC Adress indicated,
NIC tunnel timeout: 1 to 30 mn (step 1 mn)
NIC Link Report: Alarm/Even/None
Ethernet port, DNP3.0 protocol:
Protocol, IP address, subnet mask, NIC MAC
address and Gateway address indicated,
DNP time synchro: Enabled/Disabled
DNP Meas scaling:
Primary/Secondary/Normalized
RP1 Address: 7 to 34 (step 1)
RP1 Inactiv timer: 1 mn to 30 mn (step 1 mn)
Baud Rate: 9600/19200/38400 bits/s
Parity: Odd/Even/None
NIC tunnel timeout: 1 to 30 mn (step 1 mn)
NIC Link Report: Alarm/Even/None
SNTP parameters:
Primary and Secondary SNTP addresses
displayed
SNTP poll rate: 64 to 1024 s (step 1 s)
SNTP need time: 1 to 30 mn (step 1 mn)
SNTP Application
Fragment size: 100 to 2048 (step 1)
SNTP Application
fragment timeout: 1 s to 120 s (step 1 s)
SNTP SBO timeout: 1 s to 10 s (step 1 s)
Second rear port connection setting:
Protocol and Status indicated
RP2 Port configuration:
Kbus/EIA(RS)485/EIA RS232
RP2 comms mode:
IEC60870 FT1.2/10-Bit no parity
RP2 Address: 0 to 255 (step 1)
RP2 Inactivity timer: 1 to 30 mn (step 1 mn)
RP2 Baud Rate: 9600/19200/38400 bits/s