EasyManuals Logo
Home>GE>Protection Device>P444

GE P444 User Manual

GE P444
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
P44x/EN TD/
Hb6
Technical Data
(TD) 2
-8
MiCOM P40 Agile P442, P444
Power Frequency Magnetic Field Immunity
Per IEC 61000-4-8: 2001, Level 5,
100 A/m applied continuously,
1000 A/m applied for 3 s.
Per IEC 61000-4-9: 2001, Level 5,
1000 A/m applied in all planes.
Per IEC 61000-4-10: 2001, Level 5,
100 A/m applied in all planes at
100 kHz/1MHz with a burst duration of 2 s.
Conducted Emissions
Per EN 55022: 1998:
0.15 0.5 MHz, 79 dBµV (quasi peak)
66 dBµV (average)
0.5 30 MHz, 73 dBµV (quasi peak)
60 dBµV (average).
Radiated Emissions
Per EN 55022: 1998:
30 230 MHz, 40 dBµV/m at 10 m
measurement distance
230 – 1 GHz, 47 dBµV/m at 10 m
measurement distance.
EU Directives
EMC Compliance
Per 2004/108/EC:
Compliance to the European Commission
Directive on EMC is claimed via the Technical
Construction File route. Product Specific
Standards were used to establish conformity:
EN50263: 2000
Product Safety
Per 2006/95/EC:
Compliance with European Commission Low
Voltage Directive. Compliance is demonstrated
by reference to generic safety standards:
IEC 60255-27:2005
CE
R&TTE compliance
Radio and telecommunication terminal
equipment (R&TTE) directive 99/5/EC.
Compliance demonstrated by compliance to
both the EMC directives on low voltage
directive down to 0 V.
Applicable to rear communication ports.
Mechanical Robustness
Vibration Test
Per IEC 60255-21-1: 1996
Response Class 2
Endurance Class 2
Shock and Bump
Per IEC 60255-21-2: 1995
Shock response Class 2
Shock withstand Class 1
Bump Class 1
Seismic Test
Per IEC 60255-21-3: 1995
Class 2
Cyber Security
(where applicable)
Implementation
Following measures have been implemented:
Four level access,
Password strengthening,
Disabling of unused application and
physical ports,
Inactivity timer,
Storage of security events,
NERC-compliant default display.
Standards
NERC CIP (North American Electric
Reliability Corporation Critical
Infrastructure Protection, USA):
CIP-002-1, CIP-003-1, CIP-004-1,
CIP-005-1, CIP-006-1, CIP-007-1,
CIP-008-1 and CIP-009-1
BDEW (Germany),
ANSI ISA 99 (USA), IEEE 1686,
IEC 62351, ISO/IEC 27002,
NIST SP800-53 (National Institute of
Standards and Technology, USA),
CPNI Guidelines (Centre for the Protection
of National Infrastructure, UK).
IEC 61850-9-2 Ethernet board
(option)
connexion RJ45 or optical fibre
Antialiasing filter
Number of logical nodes: up to 6
Time-delay at message
reception: 0 to 3 ms
Safety control:
- presence test alarm,
- synchronization alarm,
- quality alarm,
independent per logical node

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P444 and is the answer not in the manual?

GE P444 Specifications

General IconGeneral
BrandGE
ModelP444
CategoryProtection Device
LanguageEnglish