MiCOM P40 Agile P442, P444
Power Frequency Magnetic Field Immunity
Per IEC 61000-4-8: 2001, Level 5,
∗ 100 A/m applied continuously,
∗ 1000 A/m applied for 3 s.
Per IEC 61000-4-9: 2001, Level 5,
∗ 1000 A/m applied in all planes.
Per IEC 61000-4-10: 2001, Level 5,
∗ 100 A/m applied in all planes at
100 kHz/1MHz with a burst duration of 2 s.
Conducted Emissions
Per EN 55022: 1998:
∗ 0.15 – 0.5 MHz, 79 dBµV (quasi peak)
66 dBµV (average)
∗ 0.5 – 30 MHz, 73 dBµV (quasi peak)
60 dBµV (average).
Radiated Emissions
Per EN 55022: 1998:
∗ 30 – 230 MHz, 40 dBµV/m at 10 m
measurement distance
∗ 230 – 1 GHz, 47 dBµV/m at 10 m
measurement distance.
EU Directives
EMC Compliance
Per 2004/108/EC:
Compliance to the European Commission
Directive on EMC is claimed via the Technical
Construction File route. Product Specific
Standards were used to establish conformity:
∗ EN50263: 2000
Product Safety
Per 2006/95/EC:
Compliance with European Commission Low
Voltage Directive. Compliance is demonstrated
by reference to generic safety standards:
∗ IEC 60255-27:2005
CE
R&TTE compliance
Radio and telecommunication terminal
equipment (R&TTE) directive 99/5/EC.
Compliance demonstrated by compliance to
both the EMC directives on low voltage
directive down to 0 V.
Applicable to rear communication ports.
Mechanical Robustness
Vibration Test
Per IEC 60255-21-1: 1996
Response Class 2
Endurance Class 2
Shock and Bump
Per IEC 60255-21-2: 1995
Shock response Class 2
Shock withstand Class 1
Bump Class 1
Seismic Test
Per IEC 60255-21-3: 1995
Class 2
Cyber Security
(where applicable)
Implementation
Following measures have been implemented:
∗ Four level access,
∗ Password strengthening,
∗ Disabling of unused application and
physical ports,
∗ Inactivity timer,
∗ Storage of security events,
∗ NERC-compliant default display.
Standards
∗ NERC CIP (North American Electric
Reliability Corporation – Critical
Infrastructure Protection, USA):
CIP-002-1, CIP-003-1, CIP-004-1,
CIP-005-1, CIP-006-1, CIP-007-1,
CIP-008-1 and CIP-009-1
∗ BDEW (Germany),
∗ ANSI ISA 99 (USA), IEEE 1686,
∗ IEC 62351, ISO/IEC 27002,
∗ NIST SP800-53 (National Institute of
Standards and Technology, USA),
∗ CPNI Guidelines (Centre for the Protection
of National Infrastructure, UK).
IEC 61850-9-2 Ethernet board
(option)
∗ connexion RJ45 or optical fibre
∗ Antialiasing filter
∗ Number of logical nodes: up to 6
∗ Time-delay at message
reception: 0 to 3 ms
∗
Safety control:
- presence test alarm,
- synchronization alarm,
- quality alarm,
independent per logical node