EasyManuals Logo
Home>GE>Protection Device>P444

GE P444 User Manual

GE P444
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #97 background imageLoading...
Page #97 background image
Setting
P44x/EN ST/Hb
6
MiCOM P40 Agile
P442, P444 (ST) 4-
23
Menu text Default setting
Setting range
Step size
Min Max
GROUP 1: POWER SWING
Stable swing 1 1 255 1
Threshold of number of Stable Swings. Triggers DDB #353 when reached.
Setting of the number of steps to confirm Stable Swing condition.
2.4 Directional and non-directional overcurrent protection (“Back-up I>” menu)
The overcurrent protection included in the P442 and P444 relays provides two stage non-
directional / directional three-phase overcurrent protection and two non-directional stages
(I>3 and I>4), with independent time-delay characteristics. One or more stages may be
enabled to complement the relay distance protection. All overcurrent and directional settings
apply to all three-phases but are independent for each of the four stages. The first two
stages of overcurrent protection, I>1 and I>2 have time-delayed characteristics that are
selectable between inverse definite minimum time (IDMT), or definite time (DT).
All the stages trip three-phase only. They could be used for back up protection during a VT
failure.
The following table shows the relay menu for overcurrent protection, including the available
setting ranges and factory defaults.
Menu text Default setting
Setting range
Step size
Min Max
GROUP 1 BACK-UP I>
I>1 Function DT
Disabled, DT, IEC S Inverse, IEC V
Inverse, IEC E Inverse, UK LT Inverse,
IEEE M Inverse, IEEE V Inverse, IEEE E
Inverse, US Inverse, US ST Inverse
Sets the first phase overcurrent threshold (I>1) characteristics. The conditions are
‘disabled’, definite time (DT) or inverse definite minimum time (IDMT, see section
P44x/EN AP).
I>1 Direction Directional Fwd
Non-Directional, Directional Fwd,
Directional Rev
Sets the directional control for the first stage overcurrent element.
I>1 VTS Block Non-Directional Block, Non-Directional
When the directional control for the ‘I>1’ is set, sets the Voltage Transformer Supervision
(VTS) directionality (see section P44x/EN AP).
The operation of the VTS will block the stage
or will revert to Non-directional on operation of the VTS.
I>1 Current Set 1.50 x In 0.08 x In 10.00 x In 0.01 x In
Sets the value for the overcurrent threshold.
I>1 Time delay 1 s 0 s 100 s 0.01 s
Sets the time delay associated with I>1.
I>1 Time delay VTS 0.2 s 0 s 100 s 0.01 s
Sets the VTS time-delay. The VTS alarm will occur if VT fault occurs during more than the
VTS time-delay.
I>1 TMS 1 0.025 1.2 0.005
Sets the Time Multiplier Setting (TMS), to adjust the operating time of the IEC IDMT
characteristics.
I>1 Time Dial 7 0.5 15 0.1
Sets the time dial settings, to adjust the operating time of the IEEE/ US IDMT curves. The
Time Dial is a multiplier of the standard curve equation, to achieve the required tripping

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P444 and is the answer not in the manual?

GE P444 Specifications

General IconGeneral
BrandGE
ModelP444
CategoryProtection Device
LanguageEnglish

Related product manuals