P44x/EN TD/
Hb6
Technical Data
(TD) 2
-16
MiCOM P40 Agile P442, P444
US Inverse
US Short Time Inverse
IN> (%max) 10% to 100% (step 1%)
I2>1 / I2>2 Directional:
Non-directional,
Directional forward
Directional reverse
I2>1 / I2>2 VTS Block: Block/Non-directional
I2>1 / I2>2 current set: 0.08×In to 4.00×In
(step 0.01×In)
I2>1 / I2>2 Time-delay:0 to 100 s (step 0.01 s)
I2>1 / I2>2 Time VTS:0 to 100 s (step 0.01 s)
I2>1 / I2>2 TMS: 0.025 to 1.2 (step 0.005)
I2>1 / I2>2 Time Dial: 0.01 to 100 (step 0.01)
I2>1 / I2>2 Reset
characteristics: DT or Inverse
I2>1 / I2>2 tReset 0 to 100 s (step 0.01 s)
I2>3 Status / I2>4 Status: Enabled/Disabled
I2>3 / I2>4 Directional:
Non-directional,
Directional forward
Directional reverse
I2>3 / I2>4 VTS Block: Block/Non-directional
I2>3 / I2>4 current set: 0.08×In to 32.00×In
(step 0.01×In)
I2>3 / I2>4 Time-delay:0 to 100 s (step 0.01 s)
I2>3 / I2>4 Time VTS:0 to 100 s (step 0.01 s)
I>2 Char angle 95° to +95° (step 1°)
MAXIMUM OF RESIDUAL POWER –
ZERO SEQUENCE POWER
Zero Sequence Power Status:
Activated/Disabled
K Time delay factor: 0 to 2 (step 0.2)
Basis Time Delay: 0 to 10 s (step 0.01 s)
Residual current: 0.05×In to 1×In
(step 0.01×In)
P0 threshold: 0.3 to 6.0 VA (step 30 mVA)
BROKEN CONDUCTOR DETECTION
Broken conductor: Enabled/Disabled
I2/I1 setting: 0.2 to 1 (step 0.01)
I2/I1Time Delay: 0 to 100 s (step 1 s)
I2/I1 Trip: Enabled/Disabled
DIRECTIONAL AND NON-DIRECTIONAL
EARTH FAULT OVERCURRENT
PROTECTION
Earth Fault O/C
Directional and non directional
IN> protections:
IN>1, IN>2 (range 0.0810×In)
Non directional IN> protections:
IN>3, IN>4 (range 0.0832×In)
IN>1 Function / IN>2 Function:
Disabled,
Definite Time (DT),
IEC Standard inverse
IEC Very inverse
IEC Extremely inverse
UK Long Time Inverse,
IEEE Moderately Inverse,
IEEE Very Inverse
IEEE Extremely Inverse
US Inverse
US Short Time Inverse
IN> (%max) 10% to 100% (step 1%)
IN>1 / IN>2 Directional:
Non-directional,
Directional forward
Directional reverse
IN>1 / IN>2 VTS Block: Block/Non-directional
IN>1 / IN>2 current set: 0.08×In to 10.00×In
(step 0.01×In)
IN>1 / IN>2 Time-delay:0 to 200 s (step 0.01 s)
IN>1 / IN>2 Time VTS:0 to 200 s (step 0.01 s)
IN>1 / IN>2 TMS: 0.025 to 1.2 (step 0.005)
IN>1 / IN>2 Time Dial: 0.5 to 15 (step 0.01)
IN>1 / IN>2 Reset
characteristics: DT or Inverse
IN>1 / IN>2 tReset 0 to 100 s (step 0.01 s)
IN>3 Status / IN>4 Status: Enabled/Disabled
IN>3 / IN>4 Directional:
Non-directional,
Directional forward
Directional reverse
IN>3 / IN>4 VTS Block: Block/Non-directional
IN>3 / IN>4 current set: 0.08×In to 32.00×In
(step 0.01×In)
IN>3 / IN>4 Time-delay:0 to 200 s (step 0.01 s)
IN>3 / IN>4 Time VTS:0 to 200 s (step 0.01 s)
IN> Directional
IN2 Char angle 95° to +95° (step 1°)
Polarisation:
Zero Sequence,
Negative Sequence.