Technical Data
P44x/EN TD/Hb
6
MiCOM P40 Agile P442, P444
(TD) 2-
17
AIDED DIRECTIONAL EARTH FAULT
(DEF) OVERVOLTAGE PROTECTION
Aided DEF Status: Enabled/Disabled
Polarisation:
Zero Sequence,
Negative Sequence.
V> Voltage set: 0.5 V to 20 V (step 0.01 V)
IN Forward: 0.05×In to 4×In (step0.01×In)
Time delay: 0s to 10 s (step 0.1 s)
Scheme logic: Shared/Blocking/Permissive
Tripping: Three Phase/Single Phase
Tp: 0 to 1000 ms (step 2 ms)
IN Rev Factor: 0 to 1 (step 0.1)
THERMAL OVERLOAD
Thermal characteristics:
Disabled/Single/Dual
Thermal trip:
0.08×In to 3.2×In (step 0.01×In)
Thermal alarm: 50% to 100% (step 1%)
Time constant 1: 1 mn to 200 mn (step 1 mn)
Time constant 2: 1 mn to 200 mn (step 1 mn)
RESIDUAL OVERVOLTAGE
VN Type: Residual/Homopolar
VN>1 function: Disabled/DT/IDMT
VN>1 voltage set: 1 V to 180 V (step 1 V)
homopolar: 0.5 V to 60 V (step 0.5 V)
VN>1 Time delay: 0 s to 100 s (step 0.01 s)
VN>1 TMS: 0.5 to 100 (step 0.5)
VN>1 tReset: 0 to 100 s (step 0.5 s)
VN>2 Status: Enabled/Disabled
VN>2 voltage set: 1 V to 180 V (step 1 V)
homopolar: 0.5 V to 60 V (step 0.5 V)
VN>2 Time delay: 0 s to 100 s (step 0.01 s)
(software version C7.x only)
UNDERCURRENT PROTECTION
I< mode (threshold activation):
I<1 status: activated/deactivated
I<2 status: activated/deactivated
I<1 status: Enabled/Disabled
I<1 current set 0.08×I1 to 4×I1
(step 0.01×I1)
I<1 Time Delay: 0 to 100 s (step 0.01 s)
I<2 status: Enabled/Disabled
I<2 current set 0.08×I1 to 4×I1
(step 0.01×I1)
I<2 Time Delay: 0 to 100 s (step 0.01 s)
VOLTAGE PROTECTION
V< & V> modes (threshold activation):
V<1 function: activated/deactivated
V<2 status: activated/deactivated
V<3 status: activated/deactivated
V<4 status: activated/deactivated
V>1 function: activated/deactivated
V>2 status: activated/deactivated
V>3 status: activated/deactivated
V>4 status: activated/deactivated
Undervoltage
V< Measurement mode:
PhaseNeutrel,
PhasePhase
V<1 function: Disabled/DT/IDMT
V<1 voltage set 10 to 120 V (step 1 V)
V<1 Time Delay: 0 to 100 s (step 0.01 s)
V<1 TMS: 0.5 to 100 (step 0.5)
V<2, V<3 or V<4 status: Enabled/Disabled
V<2, V<3, V<4
voltage set:
10 to 120 V (step 1 V)
V<2, V<3 or V<4 Time Delay:
0s to 100 s (step 0.01 s)
Overvoltage
V> Measurement mode:
PhaseNeutral,
PhasePhase,
Independent
V> % Hysteresis 0.1 to 2 % (step 1 %)
V>1 function: Disabled/DT/IDMT
V>1 voltage set 10 to 120 V (step 1 V)
V>1 Time Delay: 0 to 100 s (step 0.01 s)
V>1 TMS: 0.5 to 100 (step 0.5)
V>2, V>3 or V>4 status: Enabled/Disabled
V>2, V>3, V>4 voltage set:
10 to 120 V (step 1 V)
V>2, V>3 or V>4 Time Delay:
0 s to 100 s (step 0.01 s)
FREQUENCY PROTECTION
Underfrequency
F<1 Status: Disabled/Enabled
F<1 Setting: 45 Hz to 65 Hz (step 0.01 Hz°
F<1 Time Delay: 0 to 100 s (step 0.01 s)
F<2, F<3 or F<4 Status: Disabled/Enabled
F<2, F<3 or F<4 Setting:
45 Hz to 65 Hz (step 0.01 Hz°
F<2, F<3 or F<4 Time Delay:
0 to 100 s (step 0.01 s)
Overfrequency
F>1 Status: Disabled/Enabled
F>1 Setting: 45 Hz to 65 Hz (step 0.01 Hz°
F>1 Time Delay: 0 to 100 s (step 0.01 s)
F>2 Status: Disabled/Enabled
F>2 Setting: 45 Hz to 65 Hz (step 0.01 Hz°
F>2 Time Delay: 0 to 100 s (step 0.01 s)