P44x/EN TD/Hb
MiCOM P40 Agile P442, P444
(TD) 2-
SETTINGS, MEASUREMENTS
AND RECORDS LIST
SETTINGS LIST
GLOBAL SETTINGS (SYSTEM DATA):
Language:
English/French/German/Spanish/Italian/
Chinese (ordering option)
Frequency: 50/60 Hz
CONFIGURATION
Setting Group:
Select via Menu
Select via Opto
Active Settings: Group 1/2/3/4
Setting Group 1: Disabled/Enabled
Setting Group 2: Disabled/Enabled
Setting Group 3: Disabled/Enabled
Setting Group 4: Disabled/Enabled
Distance Protection: Disabled/Enabled
Power Swing: Disabled/Enabled
Back-Up I>: Disabled/Enabled
Negative Sequence
overcurrent: Disabled/Enabled
Broken Conductor: Disabled/Enabled
Earth Fault overcurrent
protection: Disabled/
Zero sequence power/
Earth fault overcurrent
Aided Directional Earth
Fault (DEF): Disabled/Enabled
Voltage Protection: Disabled/Enabled
Circuit Breaker Fail & I<: Disabled/Enabled
Supervision (Voltage,
Current or Capacitive
Voltage Transformer): Disabled/Enabled
System Checks: Disabled/Enabled
Thermal Overload: Disabled/Enabled
I< Protection: Disabled/Enabled
Residual Overvoltage
protection: Disabled/Enabled
Frequency Protection: Disabled/Enabled
Internal Autoreclose: Disabled/Enabled
Input Labels: Invisible/Visible
Output Labels: Invisible/Visible
CT & VT Ratios: Invisible/Visible
Record Control: Invisible/Visible
Disturbance Recorder: Invisible/Visible
Measure't Setup: Invisible/Visible
Communication Settings: Invisible/Visible
Commission Tests: Invisible/Visible
Setting Values: Primary/Secondary
Control Input: Invisible/Visible
Control Input Config: Invisible/Visible
Control Input Labels: Invisible/Visible
Direct Acces: Disabled/Enabled
InterMiCOM: Disabled/Enabled
Ethernet NCIT: Invisible/Visible
Function key: Invisible/Visible
RP1 / RP2 Read only Disabled/Enabled
NIC Read only Disabled/Enabled
PSL Timers: Invisible/Visible
RearPortt1ReadOnly Disabled/Enabled
RearPort2ReadOnly Disabled/Enabled
RearNICReadOnly Disabled/Enabled
LCD Contrast: (Factory pre-set)
DISTANCE PROTECTION
Line setting
Line Length (Ln): 0.3 to 1000 km (step 0.010)
or 0.2 to 625 miles (step 0.005)
Line Impedance:
0.001×I1 to 500×I1 (step 0.001×I1)
Positive sequence angle (Line Angle, ϑ
1
):
–90.0° to +90° (step 0.1°)
Zone setting
Zone Status:
∗ Z1X Enabled/Disabled
∗ Z2 Enabled/Disabled
∗ ZP Enabled/Disabled
∗ ZQ Enabled/Disabled
∗ Z3 Enabled/Disabled
∗ Z4 Enabled/Disabled
Z1 (Impedance reach:) 0.001/In to 500/In Ω
(step 0.001/In Ω)
Z1X 0.001/In to 500/In Ω
(step 0.001/In Ω)
kZ1 residual
compensation factor: 0 to 7 (step 0.001)
KZ1 residual
compensation angle: 0 to +360° (step 0.1
°)
R1G (Resistive reach for
phase-earth fault):
0 Ω to 400/In Ω (step 0.01/In Ω)
R1Ph (Resistive reach
for phase-phasefault):
0 Ω to 400/In Ω (step 0.01/In Ω)
tZ1 (time-delay
for Zone 1): 0 to 10 s (step 0.002 s)
Z2: 0.001/In to 500/In Ω (step 0.001/In/Ω)
kZ2 res comp: 0 to 7 (step 0.001)
kZ2 Angle: 0 to 360° (step 0.1°)
R2G: 0 Ω to 400/In Ω (step 0.01/In Ω)
R2Ph: 0 Ω to 400/In Ω (step 0.01/In Ω)
tZ2: 0 to 10 s (step 0.002 s)
Z3: 0.001/In to 500/In Ω (step 0.001/In/Ω)
kZ3/4 res comp: 0 to 7 (step 0.001)
kZ3/4 Angle: 0 to 360° (step 0.1°)
R3G-R4G: 0 Ω to 400/In Ω (step 0.01/In Ω)
R3Ph-R4Ph: 0 Ω to 400/In Ω (step 0.01/In Ω)
tZ3: 0 to 10 s (step 0.002 s)
Z4: 0.001/In to 500/In Ω (step 0.01/In Ω)
tZ4: 0 to 10 s (step 0.01 s)
Zone P – Directionality Forward/Reverse
Zp: 0.001/In to 500/In Ω (step 0.001/In/Ω)
kZp res comp: 0 to 7 (step 0.001)
kZp Angle: 0 to 360° (step 0.1°)
RpG: 0 Ω to 400/In Ω (step 0.01/In Ω)
RpPh: 0 Ω to 400/In Ω (step 0.01/In Ω)
tZp: 0 to 10 s (step 0.002 s)
Zone Q – Directionality Forward/Reverse
Zq: 0.001/In to 500/In Ω (step 0.001/In/Ω)
kZq res comp: 0 to 7 (step 0.001)
kZq Angle: 0 to 360° (step 0.1°)
RqG: 0 Ω to 400/In Ω (step 0.01/In Ω)
RqPh: 0 Ω to 400/In Ω (step 0.01/In Ω)
tZq: 0 to 10 s (step 0.002 s)