EasyManuals Logo
Home>GE>Protection Device>P444

GE P444 User Manual

GE P444
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #244 background imageLoading...
Page #244 background image
P
44x/EN AP/Hb6
Application Notes
(AP) 5
-92 MiCOM P40 Agile
P442, P444
4.2 Load blinding (load avoidance)
Load blinders are provided for both phase and ground fault distance elements, to prevent
misoperation (mal-tripping) for heavy load flow. The purpose is to configure a blinder
envelope which surrounds the expected worst case load limits, and to block tripping for any
impedance measured within the blinded region. Only a fault impedance which is outside of
the load area is allowed to cause a trip. The blinder characteristics are shown in
Figure 62: Load blinder characteristics
.
Figure 62: Load blinder characteristics
o R< Blinder Lim denotes the Load/B Resistance setting. This sets the cutoff of the
underimpedance .
o ß denotes the Load/B Angle setting. This sets the angle of the two blinder boundary
lines - the gradient of the rise or fall with respect to the resistive axis.
The P44x has a facility to allow the load blinder to be bypassed any time if:
The measured voltage for the phase in question falls below an undervoltage V<
setting.
A Delta Transition is confirmed. If load Blinder is enabled, an alternative Voltage Delta
threshold is used. A transition is confirmed by checking the values of V AND I. If
three consecutive samples for at least one loop are:
V > threshold VLB,
where threshold VLB = [ ((Un - Load Blinder V<) / Un) 0.1 ] Un
V threshold VLB is limited to 10% to 50% of Un
and
I > threshold l, where threshold I = 0.2 In.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P444 and is the answer not in the manual?

GE P444 Specifications

General IconGeneral
BrandGE
ModelP444
CategoryProtection Device
LanguageEnglish

Related product manuals