Application Notes
P44x/EN AP/Hb
6
MiCOM P40 Agile P442, P444
(AP) 5-
65
TOR Trip logic results
Type of Fault
TOR selected Logic
Fault in Z1
Fault in Z2
Fault in Zp
(Zq)
forward
Fault in Zp
(Zq)
reverse
Fault in Z3
Fault in Z4
TOR Z1 Enabled
1
TOR trip
T0
Dist trip
T2
Dist trip
TZp
Dist trip
TZp
Dist trip
T3
Dist trip
T4
TOR Z2 Enabled
1
TOR trip
T0
TOR trip
T0
Dist trip
TZp
Dist trip
TZp
Dist trip
T3
Dist trip
T4
TOR Z3 Enabled
1
TOR trip
T0
TOR trip
T0
TOR trip
T0
Dist trip
TZp
TOR trip
T0
Dist trip
T4
TOR All Zone
1
TOR trip
T0
TOR trip
T0
TOR trip
T0
TOR trip
T0
TOR trip
T0
TOR trip
T0
TOR Dist.Scheme
(logic POP/PUP)
1
Dist trip
T1
Dist trip
T2
Dist trip
TZp
Dist trip
TZp
Dist trip
T3
Dist trip
T4
SOTF Trip logic results
Type of Fault
SOTF
selected Logic
Fault in Z1
Fault in Z2
Fault in Zp
(Zq)
forward
Fault in Zp
(Zq)
reverse
Fault in Z3
Fault in Z4
SOTF All Zone
1
SOTF trip
T0
SOTF trip
T0
SOTF trip
T0
SOTF trip
T0
SOTF trip
T0
SOTF trip
T0
SOTF Z1 enabled
1
SOTF trip
T0
DIST trip
T2
(2)
DIST trip
TZp
(2)
DIST trip
T3
(2)
DIST trip
T4
(2)
SOTF Z2 enabled
1
SOTF trip
T0
SOTF trip
T0
DIST trip
TZp
(2)
DIST trip
T3
(2)
DIST trip
T4
(2)
SOTF Z3 enabled
1
SOTF trip
T0
SOTF trip
T0
SOTF trip
T0
SOTF trip
T0
DIST trip
T4
(2)
SOTF Z1+Rev
(with Zp forward)
1
SOTF trip
T0
DIST trip
T2
(2)
DIST trip
TZp
(TZq)
(2)
DIST trip
T3
(2)
SOTF trip
T0
SOTF Z2+Rev
(with Zp forward)
1
SOTF trip
T0
SOTF trip
T0
DIST trip
TZp
(TZq)
(2)
DIST trip
T3
(2)
SOTF trip
T0
SOTF Z1+Rev
(with Zp reverse)
1
SOTF trip
T0
DIST trip
T2
SOTF trip
T0
DIST trip
T3
(2)
DIST trip
T4
(2)
SOTF Z2+Rev
(with Zp reverse)
1
SOTF trip
T0
SOTF trip
T0
SOTF trip
T0
DIST trip
T3
(2)
DIST trip
T4
(2)
SOTF Dist. Sch. (Zp fwd)
(With a 3Plogic)
1
SOTF trip
T1
SOTF trip
T2
SOTF trip
TZp(TZq)
SOTF trip
T3
SOTF trip
T4
SOTF Disabled
(Dist. scheme & 1P)
1
DIST trip
T1
(1)
DIST trip
T2
DIST trip
(1)
TZp(TZq)
DIST trip
T3
DIST trip
T4
No setting in SOTF
(3)
(All Bits at 0) & No I>3
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DIST trip
T1
(1)
DIST trip
T2
DIST trip
TZp(TZq)
DIST trip
T3
DIST trip
T4
Level detectors
1
SOTF trip
T0
SOTF trip
T0
SOTF trip
T0
SOTF trip
T0
SOTF trip
T0
(1): the distance trip logic is applied (trip 1 pole is autorized)
(2): if Tx < 500 ms
(3): if SOTF-TOR by the I>3 overcurrents is deactivated (next section).
3.2.7.4 Switch-on-to-Fault and Trip-on-Reclose by the I>3 Overcurrent Element (not filtered for
inrush current):
Inside the 500 ms time window initiated by the SOTF-TOR logic, an instantaneous 3 phases
trip logic signal will be issued if a fault current is measured exceeding the I>3 threshold value
(‘Group 1/Back-up I>’ menu) is measured.