EasyManuals Logo
Home>GE>Protection Device>P444

GE P444 User Manual

GE P444
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #218 background imageLoading...
Page #218 background image
P
44x/EN AP/Hb6
Application Notes
(AP) 5
-66 MiCOM P40 Agile
P442, P444
After the 500 ms TOR-SOTF time windows has ended, the I>3 overcurrent element remains
in service with a trip time delay equal to the setting Group 1/Back-up I>/I>3 Time Delay.
This element would trip for close-up high current faults, such as those where maintenance
earth clamps are inadvertently left in position on line energisation.
The ‘I>3 Time Delay’ element can be permanently enabled, or enabled only for SOTF or
TOR (Figure 43). It is also used to detect close-up faults (in SOTF-TOR tripping logic no
time-delay is applied, DDB:'I>3start').
3.2.7.5 Switch on to Fault by Level Detectors
The SOTF level detectors (Bit 6 in the SOTF logic), allows an instantaneous 3-phase trip
from any low set I< level detector (Figure 43), provided that its corresponding Live Line level
detector has not picked up within 20 ms. When closing a circuit breaker to energise a healthy
line, current would normally be detected above setting, but no trip results as the system
voltage rapidly recovers to near nominal. Only when a line fault is present will the voltage fail
to recover, resulting in a trip.
SOTF trip by level detectors per phase: If V
phase
< 70% Vn AND if I
phase
> 5% In for 20 ms (to
avoid any maloperation due to an unstable contact during the reclose command signal), an
instantaneous trip command is issued.
3.2.7.6 Inputs /Outputs in TOR / SOTF Logic
The following DDB are used or available for TOR / SOTF logic (see section P44x/EN PL):
Inputs:
Man Close CB,
AR Reclaim,
CB aux A,
CB aux B,
CB aux C.
Outputs:
SOTF Enable,
TOR Enable,
TOC Start A,
TOC Start B,
TOC Start C,
Any Pole Dead,
All Pole Dead,
SOTF-TOR Trip.
3.2.7.7 Logic Diagram
In the SOTF-TOR logic diagram, the following logic name accronyms are used:
Ia<, Ib< or Ic<: No current detected (I< threshold, by default 5% In, or I< CB Fail),
Va>, Vb> or Vc>: Live voltage detected (V Live Line threshold, fixed at 70% Vn),
Z1, Z1 + Z2, Z1 + Z2 + Z3, Z4, Zp, All Zones: Zones detected (+ = OR),
'Dist Trip A', 'B' or 'C' (DDB): Trip (phase A, B or C) by distance logic,
'I3> Start' (DDB): Detection by I>3 overcurrents (not filtered by inrush),
'TOC Start A', 'B' or 'C' (DDB): Trip On Close on phase A, B or C,
'TOR (or SOTF) All Zones': TOR (or SOTF) logic enabled for all zones (distance
start).
Settings are set using ‘Distance schemes / TOR-SOTF Mode’ cell.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P444 and is the answer not in the manual?

GE P444 Specifications

General IconGeneral
BrandGE
ModelP444
CategoryProtection Device
LanguageEnglish

Related product manuals