Line connection and line-side power components
3.10 Combination options, Line Modules with line reactors and line filters
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
135
Combination options, Line Modules with line reactors and line filters
Table 3- 28 Combination options, Active Line Modules with line filters, line reactors and Active Interface Modules
Features that can be achieved
DC link
step
up factor
or rectified
value B6
Total cable length for radio interference
suppression according to EN 61800-3
Can be
operated
on an IT
line sys-
tem
1.4 … 1.6
● ● x 1.4 ... 2
2)
- 350 630 850 Yes
1)
1)
● ● x x 350 630 630 850 No
Remove connection bracket
2)
The motor insulation strength must be taken into account
Note
Ideally, new systems using Active Line Modules should be designed with Active Interface
Modules as line connection components.
Table 3- 29 Combination options, Smart Line Modules with line filters and line reactors
Features that can be achieved
DC link step
up factor or
rectified
value B6
Total cable length for radio interference sup-
pression according to EN 61800-3
Can be
operated
on an IT
line sys-
tem
1.35