Line Modules Booksize
4.5 Active Line Modules with cold plate
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
207
Table 4- 33 Technical data for Active Line Modules with cold plate cooling
25-5AA3 +
Active
Interface
Module
1)
1)
2)
Rated power (S1)
Infeed power
S6 duty (40 %)
kW (P
n
)
kW (P
S6
)
16
21
36
47
55
71
55
71
80 (64)
1)
106 (85)
1)
120 (84)
1)
145 (116)
1)
Continuous regenerative
power
Peak regenerative power
kW
16
36
55
55
80 (64)
1)
120 (84)
1)
Line voltage
Line frequency
V
ACrms
Hz
3 AC 380 … 480 ±10 % (- 15 % < 1 min)
47 … 63
DC link voltage
Overvoltage trip
3)
V
DC
V
DC
DC
510 … 720
820 ± 2 %
Rated input current:
for AC 400 V
input current:
for AC 380 V
for AC 480 V
for AC 400 V; S6 (40 %)
for AC 400 V; peak current
A
AC
A
AC
A
AC
A
AC
AC
25
26
21
32
55
58
46
71
84
88
70
108
84
88
70
108
122 (98)
1)
128 (102)
1)
102 (82)
1)
161 (129)
1)
182 (127)
1)
192 (134)
1)
152 (106)
1)
220 (154)
1)
Rated DC link current:
for 600 V
DC link current:
at 600 V DC; S6 (40 %)
at 600 V DC; peak current
A
DC
A
DC
27
35
60
79
92
121
92
121
134 (99)
1)
176 (141)
1)
200 (140)
244 (171)
1)
Current carrying capacity
DC link busbars
Reinforced DC link busbars
A
ACrms
A
ACrms
ACrms
100
150
200
--
200
--
200
--
200
--
200
Electronics current drawn
at 24 V DC
(including electronics loss-
es, see Power loss tables
W 280.4 655.2 927.6 927.6 1383.6 2243.2
Active Line Module
μF
710
1410
1880
1880
2820
3760