Line connection and line-side power components
3.11 Line connection variants
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
147
3.11.3.5
Operating line connection components via an isolating transformer
An isolating transformer converts the line supply type of the plant or system (e.g. IT system)
to a TN system. Additional voltage adaptation to the permissible voltage tolerance range is
possible.
An isolating transformer must be used in the following cases:
The insulation of the Motor Module and/or the motor is not suitable for the voltages that
occur.
There is no compatibility with an existing residual-current protective device.
The installation altitude is greater than 2000 m above sea level, and no TN or TT line
system with grounded neutral point is used.
A line filter should be used in a line supply system that is not a TN line supply system with
grounded neutral conductor.
An isolating transformer must have the following properties:
On the secondary side, the transformer must have a star connection.
The neutral point must be brought out.
Recommended vector group: Dyn5 or Yyn0
The neutral point must be grounded and connected to the PE of the line filter, line reactor or
AIM and Line Module (infeed).
Comment
: If the neutral point is not brought out and/or not connected, then all of the
restrictions of an IT line system apply.

Table of Contents

Other manuals for Siemens SINAMICS S120

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS S120 and is the answer not in the manual?

Siemens SINAMICS S120 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS S120
CategoryDC Drives
LanguageEnglish

Related product manuals