Line Modules Booksize
4.10 Smart Line Modules with external air cooling
Booksize Power Units
310 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Note
If the cooling air requirement is not covered by the filtered fan, the components cannot
output their specified power.
The filters with filter fan must be regularly c
hecked for dirt and cleaned if necessary.
Help with the mechanical control cabinet design is available from
:
Siemens AG
Digital Factory, DF MC MF - WKC AS
TCCCC (Technical Competence Center Cabinets Chemnitz)
Postfach 1124
09070 Chemnitz
E-mail: cc.cabinetcooling.aud@siemens.com
Table 4- 85 Technical data Smart Line Modules Booksize external air cooling
1)
Rated power S1 duty
Infeed power S6 duty (40 %)
Peak infeed power
kW (P
n
)
kW (P
S6
)
kW (P
max
)
5
6.5
10
10
13
20
16
21
35
36
47
70
55
71
91
Continuous regenerative power
kW
5
10
16
36
55
Line voltage
Line frequency
V
AC
Hz
3 AC 380 … 480 ± 10 % (-15 % < 1 min)
47 … 63
DC link voltage
Overvoltage trip
2)
V
DC
V
DC
DC
510 … 720
820 ± 2 %
Rated input current
at AC 400 V
at AC 380 V / AC 480 V
S6 duty (40 %) at AC 400 V
A
AC
A
AC
A
AC
8.1
8.6 / 6.7
10.6
16.2
17 / 12.8
21.1
27.5
29 / 24.5
35
59
62 / 51
76
90
94 / 77
106
DC link output current
at DC 600 V
at DC 540 V
S6 duty (40 %) at DC 600 V
A
DC
A
DC
A
DC
DC
8.3
9.3
11
16.6
18.5
22
27
30
35
60
67
79
92
105
138