Motor Modules Booksize
6.3 Motor Module with external air cooling
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
409
● A current derating is only applicable for output frequencies < 10 Hz.
● Current derating should be taken into account if the percentage time of operation at
frequencies < 10 Hz is more than 2 % of the daily total operating time.
● Also during load cycles, the current specified here must not be exceeded.
● When quickly passing through frequencies 0 to 10 Hz, derating does not have to be taken
into account (e.g. for positioning applications).
Note
Information about derating the output current as a function of the ambient temperature and
installation altitude is provided in Chapter "
System data (Page 46)".
Technical data for Motor Modules Booksize with 300% overload
6.3.8.1
Single Motor Modules (300% overload)
Table 6- 30 Technical data Single Motor Modules Booksize (3 to 18 A) with 300% overload
Rated current (l
n
)
Base-load current (I
H
)
Intermittent duty current (I
s6
) 40 %
A
AC
A
A
AC
2.6
3.5
4.3
6
7.7
10
15.3
24
AC
0 … 0.717 x DC-link voltage
DC
Overvoltage trip
1)
V
DC
DC
820 ± 2 %
DC
Electronics current drawn
at 24 VDC
DC
Current carrying capacity
DC-link busbars
Reinforced DC-link busbars
A
DC
A
DC
DC
100
150
2)
Based on I
n
(600 VDC; 4 kHz)
kW
1.6
2.7
4.8
9.7
(including electronics losses, see
Power loss tables (Page 756))
W 50.4 73.4 100.4 185.4