DC link components
8.6 Control Supply Module CSM
Booksize Power Units
546 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Table 8- 28 Technical data
Line voltage
V
AC
3 AC 380 … 480 ± 15 %
Rated input current
E rated
AC
DC
DC link voltage
(continuous input voltage)
V
DC
430 … 800
300 … 430 < 1 min
800 … 853 < 1 min
Supply current (at 600 V)
DC
Overvoltage tripping
V
DC
> 882
Rated output voltage V
A rated
A rated
1)
DC
Rated output power P
A rated
Overcurrent limitation for short-circuit A
DC
approx. 23
Current carrying capacity of the 24 V busbar
DC
Residual ripple (clock frequency approx. 50
mV
pp
< 100
Switching peaks (bandwidth 20 MHz)
Power loss ride-through (at 400 V AC)
Line
DC link
(see Power loss tables (Page 756))
W
W
70
65
2)
Type designation:
listed NKJH:
3RV1021-1DA10
3RV2011-1DA..
3RV2021-1DA..
2.2 … 3.2 (set value 3.2)
listed DIVQ:
3RV2711-4AD..
Class RK1, J, CC, CF
Rated current:
A
AC
6