Page #81 background image
Line connection and line-side power components
3.7 Line filters
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
81
3.7.6
Basic Line Filter for Smart Line Modules
3.7.6.1
Description
Basic Line Filters for Smart Line Modules are designed to attenuate conducted interference
emissions in accordance with the specifications contained in the relevant EMC legislation.
They are mainly effective in the frequency range from 150 kHz to 30 MHz; this is the range
relevant to ensure compliance with the appropriate standard.
Basic Line Filters for Smart Line Modules can be used in conjunction with the associated line
reactors.
Data regarding the radio interference voltage categories and maximum total cable lengths
that can be achieved
1)
see Chapter Combination options, Line Modules with line reactors
and line filters (Page 135).
Basic Line Filters are only suitable for direct connection to TN systems. An isolating
transformer is required for other power systems.
1)
Maximum total cable length = Σ motor cables, line supply conductor from line filter to Line
Module

Table of Contents

Other manuals for Siemens SINAMICS S120

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS S120 and is the answer not in the manual?

Siemens SINAMICS S120 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS S120
CategoryDC Drives
LanguageEnglish

Related product manuals