Line Modules Booksize
4.9 Smart Line Modules with internal air cooling
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
283
Table 4- 73 Technical data for Smart Line Modules in booksize format with internal air cooling
1)
Rated power S1 duty
Infeed power S6 duty (40 %)
Peak infeed power
kW (P
n
)
kW (P
S6
)
kW (P
max
)
5
6.5
10
10
13
20
16
21
35
36
47
70
55
71
91
Continuous regenerative power
kW
5
10
16
36
55
Line voltage
Line frequency
V
AC
Hz
3 AC 380 … 480 ± 10 % (-15 % < 1 min)
47 … 63
DC link voltage
Overvoltage trip
2)
V
DC
V
DC
DC
510 … 720
820 ± 2 %
Rated input current
at AC 400 V
at AC 380 V / AC 480 V
S6 duty (40 %) at AC 400 V
A
AC
A
AC
A
AC
8.1
8.6 / 6.7
10.6
16.2
17 / 12.8
21.1
27.5
29 / 24.5
35
59
62 / 51
76
90
94 / 77
106
DC link output current
at 600 V
at 540 V
S6 duty (40 %) at DC 600 V
Peak current at DC 600 V
A
DC
A
DC
A
DC
A
DC
8.3
9.3
11
16.6
16.6
18.5
22
33.2
27
30
35
59
60
67
79
118
92
105
138
178
Current carrying capacity
DC link busbars
Reinforced DC link busbars
A
DC
A
DC
DC
100
150
100
150
100
150
200
--
200
--
Electronics current drawn
at 24 V DC
(including electronics losses, see
Power loss tables (Page 756))
W 79.2 141.6 187.8 406 665.6
Smart Line Module
μF
220
330
705
1410
1880
Circuit breaker
(IEC 60947 and UL)
See Chapter Overcurrent protection using fuses and circuit breakers
Rated short-circuit current
SCCR
3)
kA 65 65 65 65 65
4)
See Chapter Combination options, Line Modules with line reactors and