Motor Modules Booksize
6.2 Motor Modules with internal air cooling
Booksize Power Units
376 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Note
Disturbance of the 18 A Single Motor Module with 300% overload during operation on a
16 kW Line Module
The m
aximum output of a 16 kW Line Module is not sufficient for the operation of an 18 A
Single Motor Module with 300% overload.
Do NOT operate an 18 A Single Motor Module with a 16 kW Line Module with 300%
overload (i.e. only operate an 18 A Single Motor Module with a 16 kW Line Module, if the
maximum current is limited to 2 x I
rated
).
Use at least a 36 kW Active Line Module or Smart Line Module for operation with 300%
overload.
Double Motor Modules (300% overload)
Table 6- 15 Technical data Double Motor Modules Booksize (2 x 3 to 2 x 9 A) with 300% overload
Rated current (l
n
)
Base-load current (I
H
)
Intermittent duty current (I
s6
) 40 %
A
AC
A
A
AC
2 x 2.6
2 x 3.5
2 x 4.3
2 x 6
2 x 7.7
2 x 10
AC
0 … 0.717 x DC-link voltage
DC-link voltage
(up to 2000 m above sea level)
V
DC
510 … 720
Overvoltage trip
1)
V
DC
DC
820 ± 2 %
DC
Electronics current drawn
at 24 VDC
A
DC
1.15
Current carrying capacity
DC-link busbars
Reinforced DC-link busbars
A
DC
A
DC
100
150
2)
Based on I
n
(600 VDC; 4 kHz)
kW
2 x 1.6
2 x 2.7
2 x 4.8
(including electronics losses, see Power loss
W 97.6 132.6 187.6
without derating
kHz
4