Motor Modules Booksize
6.2 Motor Modules with internal air cooling
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
371
Table 6- 13 Double Motor Modules Booksize (3 to 18 A) technical data
Rated current (l
n
)
Base-load current (I
H
)
Intermittent duty current (I
s6
) 40 %
max
A
AC
A
A
AC
AC
2 x 2.6
2 x 3.5
2 x 4.3
2 x 6
2 x 7.7
2 x 10
2 x 15.3
2 x 24
0 … 0.717 x DC-link voltage
d rated
DC
Overvoltage trip
2)
V
DC
820 ± 2 %
DC
Electronics current drawn
at 24 VDC
Current carrying capacity
DC-link busbars
Reinforced DC-link busbars
A
DC
A
DC
100
150
3)
Based on I
n
(600 VDC; 4 kHz)
kW
2 x 1.6
2 x 2.7
2 x 4.8
2 x 9.7
(including electronics losses, see Power loss
W 97.6 132.6 187.6 351.2
without derating
kHz
4
3
Max. permissible heat sink temperature
Applies only to Article numbers with "." = 0 ... 3
Default for 400 V line systems; undervoltage trip threshold can be reduced by up to 80 V and is adjusted to the parame-
terized rated voltage
3)
Rated power of a typical standard induction motor at 400 V 3 AC