EasyManuals Logo

Siemens SINAMICS S120 User Manual

Siemens SINAMICS S120
826 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #68 background imageLoading...
Page #68 background image
Line connection and line-side power components
3.7 Line filters
Booksize Power Units
68 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
3.7.4
Wideband Line Filter for Active Line Modules
3.7.4.1
Description
Wideband Line Filters for Active Line Modules are mainly effective in the frequency range
from 150 kHz to 30 MHz; this is the range relevant to ensure compliance with the appropriate
standard. Wideband Line Filters can also effectively limit low-frequency line harmonics of
2 kHz and above; this protects additional loads connected to the same supply system
against disturbances and damage. As a result, these line filters have an extended function
range, with which a certain degree of independence can be achieved regarding the machine
installation location with generally unknown line supply parameters (e.g. line impedance).
Wideband line filters must always be used in conjunction with a line reactor for Active Line
Modules. Active Interface Modules cannot be used.
Data regarding the radio interference voltage categories and maximum total cable lengths
that can be achieved
1)
see Chapter Combination options, Line Modules with line reactors
and line filters (Page 135).
1)
Maximum total cable length = Σ motor cables, line supply conductor from line filter to Line
Module

Table of Contents

Other manuals for Siemens SINAMICS S120

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS S120 and is the answer not in the manual?

Siemens SINAMICS S120 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS S120
CategoryDC Drives
LanguageEnglish

Related product manuals