Line Modules Booksize Compact
5.2 Smart Line Modules Booksize Compact
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
335
Table 5- 1 X1 line connection
Supply voltage:
3 AC 380 … 480 V, 50 / 60 Hz
Type: Screw terminal 7 (Page 730)
W1
PE connection Threaded hole M5 / 3 Nm
1
1)
For ring cable lugs without insulation (Page 732)
Table 5- 2 X21 EP terminal / temperature sensor
Temperature sensors: KTY84–1C130
1)
/ PT1000
1)
/
PTC
1)
/bimetallic switch with NC contact
The temperature sensor type and the temperature dis-
play can be selected via parameter and read-out.
2)
2 - Temp
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption, typical: 4 mA at 24 V
4 EP M (Enable Pulses)
Type: Screw terminal 1 (Page 730)
The temperatures are detected but not evaluated in the Smart Line Module.
2)
For further information see SINAMICS S120, Commissioning Manual