EasyManuals Logo

Lenze I95AE240F User Manual

Lenze I95AE240F
472 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #221 background imageLoading...
Page #221 background image
13.4.5 Set voltage boost
As an
alternave for the "Acvate voltage vector control (Imin controller)" funcon, a con-
stant, load independent voltage boost can be specied for low speeds (below the V/f rated
frequency) or for a motor standsll in order to opmise the starng performance.
WARNING!
Insucient cooling of the motor due to longer operaon at standsll.
If the motor is operated at standsll for a longer me - especially in case of smaller motors -
the mot
or can be destroyed by overtemperature!
Connect the PTC thermistor (single sensor according to DIN 44081 or triple sensor according
to DIN 44082) or thermal contact (normally-closed contact) 4Motor temperature monitor-
ing. ^ 272
Parameterise and acvate the 4Mot
or overload monitoring (i²*t). ^ 264
NOTICE
The voltage boost is added to the funcon 4Acvate voltage vector control (Imin control-
ler). ^ 219
Only se
t one of the two "boost" funcons.
Recommendaon: voltage vector control
For magnesing the motor, consider a sucient me from the controller enable
to the start of the speed ramp funcon generator. The bigger the motor the lon-
ger the me required for magnesaon. A motor with a power of 90 kW
requires up to 2 seconds.
Depending on the required starng torque, the voltage boost must be set so that the required
mot
or current will be available aer controller enable.
The v
oltage boost can be calculated by mulplying the stator resistance by the rated mag-
nesing current:
= ´Anlaufstrom ~ U R I
Boost s mN
0
0
U
Boost
0
0
U
Boost
Frequenz im Eckpunkt
Spannung im Eckpunkt Spannung im Eckpunkt
Frequenz im Eckpunkt
U
U
Boost
f
soll
U U
f
soll
U
0
0
0
0
Oponally, the voltage boost can be determined empirically by increasing the seng unl
the rated magnesing current ows.
The v
oltage boost is added geometrically to the voltage of the characterisc:
2 2
Kennlinie Boost
U= U U+
Parameter
Address Name / seng range / [default seng] Info
0x2B06 Voltage boost
0.0 ... [0.0] ... 100.0
V
Seng of the voltage boost for the voltage vector control.
Conguring the motor control
V
/f characterisc control for asynchronous motor (VFC open loop)
Set voltage boost
221

Table of Contents

Other manuals for Lenze I95AE240F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I95AE240F and is the answer not in the manual?

Lenze I95AE240F Specifications

General IconGeneral
BrandLenze
ModelI95AE240F
CategoryInverter
LanguageEnglish

Related product manuals