13.11 Tesng the motor control
P
arameter
Address Name / seng range / [default seng] Info
0x2825 Drive mode selecon
Seng can only be changed if the inverter is inhibi-
t
ed.
Internal service parameter
0 CiA402 operang modes
1 Manual "voltage/frequency" test mode
2 Manual "current/frequency" test mode
3 Manual "current pulse" test mode
4 Manual control mode
5 Pole posion idencaon (360°)
6 Pole posion idencaon (min. movement)
7 Pole posion idencaon (without move-
ment)
8 Inverter characterisc idencaon
9 Motor parameters idencaon
10 Lh saturaon characterisc idencaon
11 PRBS excitaon - mechanical plant
12 PRBS excitaon - current control loop
13 PRBS excitaon - speed control loop
14 PRBS excitaon - posion control loop
13.11.1 General
sengs for test modes
Wiring check by means of manual test modes
Before starng the parameter seng of the inverter, check the motor wiring (motor connec-
on / feedback connecon) for errors and funcon and correct them if required:
1.
Pr
ovided that the motor is connected in correct phase relaon and the rotang eld fre-
quency is posive, the motor
sha rotates clockwise.
2.
An exisng speed feedback in the rotor posion () generates a numerical value with posi-
ve counng direcon. If required, take correcve measures: see the table at the end of
the list.
3.
Aer the controller inhibit (0x6040) has been acvated, the following manual test modes
are available via the parameter 0x2825:
Manual "t
ension/frequency" test mode
Manual "current/frequency" test mode
The parameters for the test modes can be adapted via the parameter . Please observe the
not
es in the descripon of the respecve test mode.
Rotang
eld frequency
Display
Measure
CW 0...2047 None
2047...0 Correct motor connecon / feedback connec-
on
CCW 2047...0 None
0...2047 Correct motor connecon / feedback connec-
on
Parameter
Address Name / seng range / [default seng] Info
0x2835:001 Manual test mode: Current setpoint
0 ... [0] ... 1000 %
Seng of the r.m.s. value of a phase current for the test mode.
100 %: Mot
or rated current (0x6075)
0x2835:002 Manual test mode: Frequency
-1000.0 ... [0.0] ... 1000.0 Hz
Seng of the frequency for the test mode.
Conguring the motor control
Tesng the motor control
Gener
al sengs for test modes
277

Table of Contents

Other manuals for Lenze I95AE240F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I95AE240F and is the answer not in the manual?

Lenze I95AE240F Specifications

General IconGeneral
BrandLenze
ModelI95AE240F
CategoryInverter
LanguageEnglish

Related product manuals