16.3.2.2 Suppress diagnosc messages to the IO controller
0x285A:001 ser
ves to set which error response in the inverter suppresses the alarm message
to the IO-Controller.
Parameter
Address Name / seng range / [default seng] Info
0x285A:001 Diagnosc
sengs: Alarm supression
0x0000 ... [0x0000] ... 0xFFFF
Bit coded selecon of error responses in the inverter which suppress the
alarm message to the IO Controller.
•
Bit x = 1 ≡ suppress alarm message.
•
In the default seng "0", an alarm message is displayed for all error
responses.
Bit 0 Informaon
Bit 1 Warning
Bit 2 -
Bit 3 Trouble
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 Fault
Bit 8 Fault > CiA402
16.3.3 Process data transfer
The process data is used to control the inverter.
•
The pr
ocess data is transmied cyclically between the IO-Controller and the IO-Devices
parcipang in PROFINET.
•
The pr
ocess data can be directly accessed by the IO controller. The data in the PLC, for
instance, are directly stored in the I/O area.
•
The process data length is 1 ... 16 double words (4 ... 64 bytes) for each direcon.
•
The pr
ocess data are transmied 1 : 1 according to its sequence.
Conguring the network
PR
OFINET
Process data transfer