20 Technical data
20.1
Standards and operang condions
20.1.1 Conformies/approvals
Conformity
CE
2006/42/EC Machinery Direcve
2014/30/EU EMC Direcve (reference: CE-typical drive system)
RoHS 2011/65/EU
Restricons for the use of specic hazardous materials in electric
and electronic devices
Approval
UL UL 61800-5-1
for USA and Canada (requirements of the CSA 22.2 No. 274)
File No. E132659
up to 75 kW
20.1.2 Protecon of persons and device protecon
Enclosure
IP20 EN 60529
Informaon applies to the mounted and ready-for-use state. It
does not apply t
o the wire range of the terminals
NEMA 250 only protecon against accidental contact acc. to type 1
Open type Only in UL-approved systems
Insulaon resistance
Overvoltage category III EN 61800-5-1 0 … 2000 m a.m.s.l.
Overvoltage category II EN 61800-5-1 above 2000 m a.m.s.l.
Control circuit isolaon
Safe mains isolaon by double/reinforced insula-
on
EN 61800-5-1
Protecve measures against
Short circuit
Earth fault Earth fault strength depends on the operang status
Motor overtemperature PTC or thermal contact, I²xt monitoring
Overvoltage
Motor stalling
Leakage current
> 3.5 mA AC, > 10 mA DC EN 61800-5-1 Observe regulaons and safety instrucons!
Starng current
≤ 3 x rated mains current
20.1.3 EMC data
Actuaon on public supply systems
Implement measures to limit the radio interfer-
ence t
o be expected:
The machine or plant manufacturer is responsible for compliance
with the requirements for the machine/plant!
< 1 kW: with mains choke
EN 61000-3-2
> 1 kW at mains current ≤ 16 A: without addi-
onal measures
Mains current > 16 A: with mains choke or
mains lter, with dimensioning for rated
power.
EN 61000-3-12
Noise emission
Category C2 EN 61800-3 see rated data
Category C3 EN 61800-3 see rated data
Noise immunity
Meets requirement in compliance with EN 61800-3
Technical data
EMC da
ta
432