16.1.6.6 Quick stop acve
This device state is acve if quick stop is executed or acve.
•
Only the par
ameters of the inverter can be changed that do not require an inverter disa-
ble.
•
If the internal holding brake control (0x2820:001) is acve in the inverter, the motor brake
is closed.
•
The driv
e control is acve.
1 From all states
2 Power secon inhibited (pulse inhibit)
3 Power secon enabled
Bit paern in the CiA 402 status word (0x6041)
Bit 15 ... 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved
(specic)
Warning
acve
Operaon
inhibited
Quick stop
acve
DC bus ready
f
or operaon
Fault acve Operaon
enabled
Switched on Ready to
switch on
X X 0 0 X 0 1 1 1
X = state is not relevant
The "Enable operaon" command stops an acve quick stop.
Conguring the network
De
vice prole CiA 402
Device states
307