4.2.1.1 Generate a connecon between inverter and »EASY Starter«
For commissioning the inverter with the »EASY Starter«, a communicaon link with the inver-
t
er is required. This can be established in a wired manner only.
Addional informaon on network conguraon: 4Congure engineering port ^ 288
Further
informaon on how to create a communicaon link via "PROFINET": 4PROFI-
NET ^ 330
How to establish a communicaon to the inverter via the engineering port X16:
Precondions
•
The funconal test described in the mounng and switch-on instrucons has been com-
ple
ted successfully (without any errors or faults).
•
The inverter is ready for operaon (mains voltage is switched on).
Required accessories
•
Engineering PC with installed »EASY Starter«
•
Standard network cable
1.Plug the network cable into the engineering port X16 of the inverter.
2.Use the network cable to connect the inverter to the PC on which the »EASY Starter« is
installed.
3.Start the »EASY Starter«.
The "Add devices" dialog is shown.
4.Select the "Ethernet" connecon.
5.Click the Insert buon.
The »EASY Starter« searched for connected devices via the communicaon path selected.
When the connecon has been established successfully, the inverter is displayed in the device
list. The inverter parameters can now be accessed via the tabs of the »EASY Starter«.
Commissioning
Operang interfaces
Engineering t
ool »EASY Starter«
30