13.9.2 Motor temperature monitoring
In order to record and monitor the motor temperature, a PTC thermistor (single sensor
acc
ording to DIN 44081 or triple sensor according to DIN 44082) or thermal contact (normally-
closed contact) can be connected to the terminals T1 and T2. This measure helps to prevent
the motor from being destroyed by overheang.
Precondions
The in
verter can only evaluate one PTC thermistor! Do not connect several PTC thermistors
in series or parallel.
If several motors are actuated on one inverter, thermal contacts (NC contacts) connected
in series are to be used.
To achieve full motor protecon, an addional temperature monitoring funcon with a
separ
ate evaluaon must be installed.
By default, a wire jumper is installed between terminals X109/T1 and X109/T2, which must
be removed when the PTC thermistor or thermal contact is connected.
Details
If 1.6 kΩ < R < 4 kΩ at terminals X109/T1 and X109/T2, the monitoring funcon will be acva-
ted; see funconal test below.
If the monit
oring funcon is acvated, the response set in 0x2D49:002 will be eected.
The seng 0x2D49:002 = 0
deacvates the monitoring funcon.
If a suitable motor temperature sensor is connected to the terminals X109/T1
and X109/T2 and the r
esponse in 0x2D49:002 is set to "Fault [3]", the response
of the motor overload monitoring may be set other than "Fault [3]" in .
4Motor overload monitoring (i²*t) ^ 264
Funconal test
Connect a xed resistor to the PTC input:
R > 4 kΩ : the monitoring funcon must be acvated.
R < 1 kΩ : the monit
oring funcon must not be acvated.
Parameter
Address Name / seng range / [default seng] Info
0x2D48:002 PTC temperature sensor monitoring: Error response Seng of a response for PTC temperature monitoring.
Associated error code:
17281 | 0x4381 - RANLI_CIMES_1000_21212
0 No response
1 Fault > CiA402
2 Warning
0x2D49:001 Motor temperature monitoring: Temperature sensor
type
Selecon of the motor temperature sensor used.
0 KTY83-110
1 KTY83-110 + 2 x PTC 150 °C in series
2 KTY84-130
3 Specic characterisc
4
5 PT1000 Selecon of the motor temperature sensor used.
6 PT1000 + 2 x PTC 150 °C in series
0x2D49:002 Motor temperature monitoring: Response Selecon of the response to the triggering of the motor temperature
monitoring.
Associated error codes:
17168 | 0x4310 - Motor temperature error
17280 | 0x4380 - RANLI_CIMES_1000_02502
17282 | 0x4382 - RANLI_CIMES_1000_21218
17283 | 0x4383 - RANLI_CIMES_1000_21219
0 No response
1 Fault > CiA402
Conguring the motor control
Mot
or protecon
Motor temperature monitoring
272

Table of Contents

Other manuals for Lenze I95AE240F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I95AE240F and is the answer not in the manual?

Lenze I95AE240F Specifications

General IconGeneral
BrandLenze
ModelI95AE240F
CategoryInverter
LanguageEnglish

Related product manuals