EasyManuals Logo

Lenze I95AE240F User Manual

Lenze I95AE240F
472 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #337 background imageLoading...
Page #337 background image
Assignment of the user data depending on the data type
Depending on the data type used, the user data is assigned as follows:
Data type Length User data assignment
Byte 1 Byte 2 Byte 3 Byte 4 Byte ...
String x bytes Data (x b
ytes)
U8 1 byte Data 0x00
U16 2 bytes HIGH byte LOW byte
Data Data
U32 4 bytes HIGH word LOW word
HIGH byte LOW byte HIGH byte LOW byte
Data Data Data Data
16.3.5 Monitoring
The parameters for seng network monitoring funcons are described below.
Parameter
Address Name / seng range / [default seng] Info
0x2859:001 PROFINET monitoring: Watchdog elapsed Selecon of the response to a permanent interrupon of the communi-
caon to the IO controller.
Corr
esponding error code: 33168 | 0x8190 "PROFINET: Watchdog me-
out"
Associated error code:
33168 | 0x8190 - RANLI_CIMES_1000_20915
0 No response
1 Fault > CiA402
2 Warning
0x2859:002 PROFINET monitoring: Data exchange exited Selecon of the response to exing the "Data Exchange" state.
Corresponding error code: 33171 | 0x8191 "PROFINET: Exit Data
Exchange"
Associated error code:
33169 | 0x8191 - RANLI_CIMES_1000_21217
0 No response
1 Fault > CiA402
2 Warning
0x2859:003 PROFINET monitoring: Invalid conguraon Selecon of the response triggered by the recepon of invalid congura-
on data.
Corresponding error code: 33414 | 0x8286 "PROFINET: Conguraon
error"
Associated error code:
33415 | 0x8287 - RANLI_CIMES_1000_20916
0 No response
1 Fault > CiA402
2 Warning
0x2859:004 PROFINET monitoring: Inialisaon error Selecon of the response triggered by the occurrence of an error during
the inialisaon of the network component.
Corresponding error code: 33170 | 0x8192 "PROFINET: Inialisaon
error"
Associated error code:
33170 | 0x8192 - RANLI_CIMES_1000_20917
0 No response
1 Fault > CiA402
2 Warning
Conguring the network
PR
OFINET
Parameter data transfer
337

Table of Contents

Other manuals for Lenze I95AE240F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I95AE240F and is the answer not in the manual?

Lenze I95AE240F Specifications

General IconGeneral
BrandLenze
ModelI95AE240F
CategoryInverter
LanguageEnglish

Related product manuals