19.7 System Configuration Examples
The following shows a system configuration example in the case of the microcomputer connection.
1 System Configuration
The system configuration example illustrated below is explained in this section.
2 Communication settings on GOT side and monitor screen settings
(1) Transmission settings
Set the transmission settings of the GOT.
The transmission settings in the microcomputer connection are made at "Communication Details
Settings" on GT Designer2
Section 19.6.3 Setting communication interface (Communication settings)
(2) Monitor screen settings
The following shows the monitor screen settings in this system configuration example.
(a) Common settings
Set D20 to the screen switching device (base screen).
Setting item Setting
Transmission speed 38400bps
Data length 8 bits
Stop bit 1 bit
Parity Even
Interrupt Data Byte 1 byte
Host Address (0 to 31) 0
Format 1
1 Select [Common] [System Environment] on
GT Designer2, and display the [System
Environment].
2 Set D20 to the screen switching device (base
screen).
IBM-PC/AT-compatible PC
(Microsoft
®
Visual C++
®
Ver.6.0)