Commissioning involves the following steps:
• Basic settings:
If t
he converter has already been commissioned, then the web server jumps to the basic
settings.
The following settings are required for a brand-new converter:
– Language, date, time
• Security settings:
The settings are congured with the help of the Security Wizard.
You can nd more information in Section "Security settings (Page174)".
• Quick setup:
Menu "Commissioning" > "Quick setup"
– Entry or checking of motor and encoder data
– Limit values and I/O conguration
• Optimize motor:
Menu "Commissioning" > "Optimization"
The Optimization function measures the mechanical drive train using short test signals and
adapts the controller parameters to the mechanics installed.
• Test motor operation:
Action bar > "Control panel"
Test of motor operation using the control panel in jog mode or continuous operation
• Backup:
Menu "Backup and restore"
Siemens recommends a backup of the drive settings after commissioning.
More information
For more information about user management and security settings, see the Conguration
Manual Industrial Cybersecurity Conguration Manual (
https://
support.industry.siemens.com/cs/ww/en/view/109810578).
7.4.2.2 Quick se
tup
Overview
The converter can generally be operated without making additional settings using quick setup.
Siemens recommends that quick setup is performed to set the limit values and the I/O
conguration to optimally address the target application.
Requirement
• The drive system has been congured. The components are wired.
• Web server access is active.
Commissioning (web server)
7.4Functions and menus
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
180 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB