8.6 Carrying out guided quick startup
8.6.1 Over
view
Overview
Using the "guided quick startup", you perform the basic settings for the drive in Startdrive that
are used to avoid the following detailed settings as far as possible. All drive settings are pre-
assigned according to the required application use via these basic settings.
Requirement
• The drive has been completely created and specied in the device conguration.
Without a complete specication, the guided quick startup cannot be used and a message
appears.
• If a control is also used, it must be connected to the drive in the topology view and in the
network view. The connection between the devices must also be congured.
• Optional: The operating unit is connected to the drive via LAN (physically online).
• For activated user management (UMAC):
The function rights for editing drive data are activated for your user account.
Details on this topic are provided in Chapter "Security settings in Startdrive" of Industrial
Cybersecurity Conguration Manual (
https://support.industry.siemens.com/cs/ww/en/view/
109810578).
Commissioning (Startdrive)
8.6Carrying out guided quick startup
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 253