8.3 Basics
8.3.1 Communication inter
faces
Overview
The following interfaces are available for accessing the converter:
Interface Information
Service inter‐
face X127
The default access to Startdrive is via the service interface X127.
Ethernet interface X127 is intended for commissioning and diagnostics, which means
that it must alw
ays be accessible.
Defaults:
• IP addres
s: 169.254.11.22
• Subnet mask: 255.255.0.0
• Connection type: HTTPS
Restrictions:
• Only local acces
s is allowed.
• No networking or only local networking in a closed and locked electrical cabinet is
permissible.
• For remote access to the electrical cabinet, you must apply additional security
measures to prevent misuse through sabotage, data manipulation by unqualied
persons and interception of condential data.
Access using mobile end devices:
• If you
carry out commissioning or diagnostics using a mobile end device such as a
smartphone or tablet, you may temporarily connect the service interface X127 to
an external WLANaccess point.
PROFINET in‐
terface X150
Defaults (oine):
•
IP address: 0.0.0.0
• Subnet mask: 0.0.0.0
Requirements:
• The conv
erter and your operating unit must be located in the same subnet to ensure
an eective online connection.
• Before you can go online on a converter via PROFINET, you must assign the PROFI‐
NET interface of the converter a suitable IP address.
• The IP addresses of the service interface X127 and the PROFINET interface X150
must not be in the same subnet.