The following information of the displayed telegrams is displayed:
Table 8-6 T
elegram structure
Telegram type Status words Value Format switchover PZD
List of the status words
that are tr
ansferred in
the telegram.
Value of the proc‐
ess data (PZD)
The value of the process data
is switched to a dierent rep‐
resentation (hex, bin, dec).
Numbering and ar‐
rangement of the
process data.
PROFIdrive
3, 5, 102, 105
X X X X
Torque supplemen‐
t
ary t
elegram
750
X X X X
8.9.6 Functions
8.9.6.1 Over
view
Overview
In the "Functions" area, you can call the following functions via the secondary navigation of the
diagnostic view and make settings within them:
• Assign IP address
• Firmware update
• Assign PROFINET device name
• Reset PROFINET interface parameters
• Set time
Overview
To restore the converter to the delivery state, you need to reset the PROFINET interfaces of the
converter in addition to restoring the factory settings.
If the converter is connected to a controller while the PROFINET interfaces are being reset,
the controller assigns new interface parameters to the converter immediately after the reset.
To prevent this, switch the controller to "Stop" mode before the reset or terminate the
connection between controller and converter.
Commissioning (Startdrive)
8.9Using online diagnostic functions
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 301