3. If you want to perform extended settings, click the "Extended settings" button.
The "Machine proper
ty" dialog opens. You obtain information about the conditions under
which you can increase the speed control dynamic performance. If you wish to increase the
dynamic response, activate option "Set the current setpoint lter with loop compensation".
4. Establish an online connection to the converter if up until now you had worked in the oine
mode.
– Activate master control.
– Start the OBT.
– Check the optimization results.
– Deactivate the master control.
5. Click on "Next" to display the next quick startup step.
Result
The result of the optimization is displayed in the "Status" area. The "Optimization result" list
compares the settings changed by the optimization with the earlier settings prior to
optimization.
If optimization was not successful, repeat the optimization, possibly with modied data.
More information
For more information about One Button Tuning, see Section "Performing One Button Tuning
(Page291)".
8.6.10 "Overview" function view
8.6.10.1 Oine mode
Overview
After completing the commissioning steps in the guided quick startup, here, you will nd a
compilation of all settings that were made oine.
If necessary, you can load the settings made oine from the "Overview" function view into
the device.
Commissioning (Startdrive)
8.6Carrying out guided quick startup
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
274 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB