Description of function
As soon as the setpoint for the position within a positioning operation no longer changes, then
the converter sets the "Setpoint stationary" signal to 1. With this signal, the converter starts to
monitor the position actual value:
• As soon as the axis has reached the positioning window, the converter signals that the target
has been reached, and maintains the axis in closed-loop control.
• If the axis does not come to a standstill within the standstill monitoring time, the converter
reports fault F07450.
• If the axis does not enter the positioning window within the positioning monitoring time, the
converter reports fault F07451.
3RVLWLRQVHWSRLQW
3RVLWLRQDFWXDOYDOXH
3RVLWLRQ
VHWSRLQW
3RVLWLRQDFWXDO
YDOXH
6HWSRLQWVWDWLF
7DUJHWSRVLWLRQ
LVUHDFKHG
6WDQGVWLOOZLQGRZ
6WDQGVWLOOPRQLWRULQJWLPH
3RVLWLRQLQJZLQGRZ
3RVLWLRQLQJPRQLWRULQJWLPH
V
V
W
)
)
Y
V
D
W
Figureî™ 10-9 Standstill monitoring and positioning monitoring
10.6.3.2 Following error monitoring
Overvie
w
Following error monitoring is used to monitor the maximum deviation between the actual value
and the position setpoint.
Functions
10.6î™ Basic positioner (EPOS)
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 375