Scenario 1: The tar
get converter has the same or a higher 󹪝rmware version.
If the drive data are restored from an encrypted backup 󹪝le, then proceed as follows, see
Section "Restoring data from an encrypted backup 󹪝le (Page596)".
If the drive data are restored from an unencrypted backup 󹪝le, then proceed as follows,
see Section "Restoring data from an unencrypted backup 󹪝le (Page594)".
Scenario 2: The target converter has an older 󹪝rmware version.
The operation is canceled.
Restore the 󹪝rmware to the version of the source converter. The 󹪝rmware version can be
󹪝rmware version of the source converter.
Note
Determining t
he 󹪝rmware version of the source converter
Review the machine documentation. Alternatively: Check which 󹪝rmware version is
installed on the other converters of the same type in the machine.
Proceed as described in scenario 1.
Result
When running
up, the converter retrieves the settings from the backup 󹪝le. Commissioning has
been completed once the converter has run up.
More information
Update the connected components:
When the converter runs up after being restored, the connected components are updated.
The converter must then be switched o󹪜 and switched on.
13.1.3.2 Restoring data from an unencrypted backup 󹪝le
Requirement
You have an unencrypted backup 󹪝le of the source converter on your operating unit.
Rights required for active user management (UMAC):
"Create backup or load drive data to Startdrive"
Procedure
1. Call menu "Backup and restore" in the web server.
2. Navigate to the "Restore drive data from backup 󹪝le" area.
3. Use the "Click to select 󹪝le, or drag and drop 󹪝le here" button to select the backup 󹪝le.
4. To restore the drive data, proceed as described below depending on the speci󹪝c application.
This step is included in the following diagrams as step 3.
Corrective maintenance
13.1Service and maintenance for the converter
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
594 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS SIMOTICS S200 PROFINET and is the answer not in the manual?

Siemens SINAMICS SIMOTICS S200 PROFINET Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS SIMOTICS S200 PROFINET
CategoryServo Drives
LanguageEnglish

Related product manuals