Requirement
You have an SD card with the appropriate rmware, or you have an empty SD card with a
maximum capacity of 32GB onto which you can load the rmware.
You can download the available rmware versions at the following link (https://
support.industry.siemens.com/cs/ww/en/ps/29596/dl).
Procedure
Pr
oceed as follows to update the rmware using an SD card:
1. Switch o the converter.
2. Insert the SD card into the converter and switch on the converter.
The new rmware is installed. This process takes approximately two minutes.
RDY COM Explanation of LED displays
Firmware update is active:
• Do not switc
h o the power supply.
• Do not disconnect the motor from the converter.
- Firmware update is completed
3. Switch the converter o and remov
e the SD card.
4. Switch on the converter again. Check whether the new version is installed. The rmware
version of the converter is displayed on the home page of the web server.
More information
You can nd more information about the SD card in Section "SD card (Page72)".
13.1.3 Replacing the converter
Overview
You may only replace a converter with another converter if certain requirements are adhered to.
Corrective maintenance
13.1Service and maintenance for the converter
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
590 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB