4.8.5 EMC-compliant cable routing
Overvie
w
Power cables with a high interference level signi󹪝cantly in󹪞uence the electromagnetic 󹪝elds in
a system or a machine.
Routing cables to be compliant with EMC is a requirement for disturbance-free operation of a
system or machine.
Description
The converter connection cables have di󹪜erent interference levels:
Cables with a high level of interference:
Cable between the line 󹪝lter and converter
Motor connection cables
Cable at the converter DC link connection
Cables with a low level of interference:
Cable between the line and line 󹪝lter
Signal and data cables
EMC-compliant cable routing complies with the following requirements:
All cables are as short as possible.
All cables are routed close to the mounting plates or control cabinet frames.
Power cables with a high level of interference are routed so that there is a minimum clearance
of 20cm to cables with a low level of interference.
If the minimum clearance of 20 cm is not possible, insert separating metal panels between
the cables with a high level of interference and those with a low level of interference. The
separating metal panels are connected to the mounting plate to establish a good electrical
connection.
Cables with a high level of interference and cables with a low level of interference only cross
over at right angles.
All signal and data cables enter the control cabinet from only one side, from below, for
example.
Signal and data cables, as well as the associated equipotential bonding cables, are routed in
parallel and close to one another.
Any unused conductors of signal and data cables are grounded at both ends.
Incoming and outgoing individual conductors that are not shielded are twisted with one
another.
Alternatively, incoming and outgoing conductors are routed in parallel, but close to one
another.
Application planning
4.8EMC-compliant installation
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
94 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS SIMOTICS S200 PROFINET and is the answer not in the manual?

Siemens SINAMICS SIMOTICS S200 PROFINET Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS SIMOTICS S200 PROFINET
CategoryServo Drives
LanguageEnglish

Related product manuals