SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
105
2 Parameters
2.2 List of parameters
Description: Sets the drive unit supply voltage (3-ph. AC).
The value corresponds to the rms value of the phase-to-phase rated line supply voltage.
Dependency: The parameter can be reduced to p0210 = 70 V if p0212.0 is set.
Notice: When connected to 3-ph. 230 V AC (only booksize units) the following must be observed:
- the undervoltage and overvoltage limits change (r0296, r0297).
- when using the internal braking chopper of Basic Line Modules (20 or 40 kW) the threshold when the braking
chopper becomes active is reduced to 385 V. When using an external braking chopper, it must be ensured that a
suitable activation threshold is used.
- all of the components connected to this DC link must also be adapted to the low line supply voltage. It is especially
important that the rated DC voltage of all of the drives connected to this DC link is set with p0210 (e.g.
p0210(SERVO) = 1.35 x p0210(B_INF) = 310 V).
- it is not possible to use a Control Supply Module (CSM) to generate a 24 V supply from the DC link, as the minimum
continuous DC link voltage should not be below 430 V.
Note: The supply voltage range depends on the voltage class of the power unit.
400 V chassis units: 380 V <= p0210 <= 480 V
690 V chassis units: 500 V <= p0210 <= 690 V
400 V booksize units can also be connected to 3-ph. 230 V AC:
400 V booksize units: 180 V <= p0210 <= 480 V
A reduced supply voltage up to 70 V is possible if p0212.0 = 1 has been set.
Description: Sets the drive unit supply voltage.
AC/AC unit: The rms value of the phase-to-phase line supply voltage should be entered.
DC/AC unit: The rated DC voltage of the connection busbar should be entered.
Dependency: Set p1254, p1294 (automatic detection of the Vdc switch-on levels) = 0.
The switch-in thresholds of the Vdc_max controller (r1242, r1282) are then directly determined using p0210.
The parameter can be reduced to p0210 = 100 V if p0212.0 = 1 has been set.
Refer to: p0212
Notice: If, in the switched-off state (pulse inhibit), the supply voltage is higher than the entered value, the Vdc controller may
be automatically de-activated in some cases to prevent the motor from accelerating the next time the system is
switched on. In this case, an appropriate alarm A07401 is output.
Note: Setting ranges for p0210 as a function of the rated power unit voltage:
U_rated = 400 V:
- p0210 = 380 ... 480 V (AC/AC), 510 ... 720 V (DC/AC)
U_rated = 500 V:
- p0210 = 500 ... 600 V (AC/AC), 675 ... 900 V (DC/AC)
U_rated = 660 ... 690 V:
- p0210 = 660 ... 690 V (AC/AC), 890 ... 1035 V (DC/AC)
U_rated = 500 ... 690 V:
- p0210 = 500 ... 690 V (AC/AC), 675 ... 1035 V (DC/AC)
p0210 Drive unit line supply voltage / V_connect
B_INF Can be changed: C2(1) Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8760
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
70 [Vrms] 1000 [Vrms] 400 [Vrms]
p0210 Drive unit line supply voltage / V_connect
VECTOR_G Can be changed: C2(2), T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 [V] 63000 [V] 600 [V]

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals