2 Parameters
2.2 List of parameters
SINAMICS G130/G150
262 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the signal source for the feedback signal from the line contactor.
Recommend.: When the monitoring is activated (BI: p0860 not equal to r0863.1), then to control the line contactor, signal BO:
r0863.1 of its own drive object should be used.
Dependency: Refer to: p0861, r0863
Notice: The line contactor monitoring is de-activated if the control signal of the particular drive object is set as the signal
source for the feedback signal of the line contactor (BI: p0860 = r0863.1).
Note: The state of the line contactor is monitored depending on signal BO: r0863.1.
When the monitoring is activated (BI: p0860 not equal to r0863.1), fault F07300 is then also output if the contactor is
closed before it is controlled using r0863.1.
Description: Sets the monitoring time of the line contactor.
This time starts each time that the line contactor switches (r0863.1). If a feedback signal is not received from the line
contactor within the time, a message is output.
Dependency: Refer to: p0860, r0863
Note: The monitoring function is disabled for the factory setting of p0860.
Description: Sets the delay time for the control command of the power unit and a line contactor, if used.
Note: This means that it is possible to realize a shifted (delayed) pre-charging or power-on using a single ON command.
When the infeed units are active, before the line contactor is closed, an offset adjustment of the current measurement
is carried out for a duration of 120 ms (p3491).
Description: Display and BICO output for the status word and control word of the drive coupling.
p0860 BI: Line contactor feedback signal / Line contact feedb
B_INF, VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2634, 8734,
8834, 8934
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 863.1
p0861 Line contactor monitoring time / LineContact t_mon
B_INF, VECTOR_G Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2634, 8734,
8834, 8934
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 5000 [ms] 100 [ms]
p0862 Power unit ON delay / PU t_on
B_INF, VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2610, 8732,
8832, 8932
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 65000 [ms] 0 [ms]
r0863.0...2 CO/BO: Drive coupling status word/control word / CoupleZSW/STW
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -