59
2 Parameters
2.2 List of parameters
Note: Value 99 means the following: No encoder assigned (not configured).
Description: Displays the effective Command Data Set (CDS).
Dependency: Refer to: p0810, p0811, r0836
Note: The Command Data Set selected using a binector input (e.g. p0810) is displayed using r0836.
Description: Displays the effective Drive Data Set (DDS).
Dependency: Refer to: p0820, p0821, p0822, p0823, p0824, r0837
Note: The drive data set changeover is suppressed when selecting the motor identification, during the rotating
measurement, the encoder calibration and the friction characteristic record.
Description: Display and BICO output for the status word of the closed-loop control.
r0050.0...3 CO/BO: Command Data Set CDS effective / CDS effective
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8560
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 CDS eff bit 0 ON OFF -
01 CDS eff bit 1 ON OFF -
02 CDS eff bit 2 ON OFF -
03 CDS eff bit 3 ON OFF -
r0051.0...4 CO/BO: Drive Data Set DDS effective / DDS effective
ENC, VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8565
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DDS eff bit 0 ON OFF -
01 DDS eff bit 1 ON OFF -
02 DDS eff bit 2 ON OFF -
03 DDS eff bit 3 ON OFF -
04 DDS eff bit 4 ON OFF -
r0056.0...15 CO/BO: Status word, closed-loop control / ZSW cl-loop ctrl
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 2526
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Initialization completed Yes No -
01 De-magnetizing completed Yes No -
02 Pulse enable available Yes No -
03 Soft starting present Yes No -
04 Magnetizing completed Yes No -
05 Voltage boost when starting Active Inactive 6301
06 Acceleration voltage Active Inactive 6301
07 Frequency negative Yes No 6719
08 Field weakening active Yes No -
09 Voltage limit active Yes No 6714
10 Slip limit active Yes No 6310

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals