2 Parameters
2.2 List of parameters
SINAMICS G130/G150
58 List Manual (LH2), 04/2014, A5E03263479A
Bit 27 = 1 (enable signal missing), if:
- de-magnetizing has still not been completed (only for vector).
Bit 28 = 1 (enable signal missing), if:
- the holding brake is closed or has still not been opened.
Bit 29 = 1 (enable signal missing), if:
- the cooling unit ready signal via binector input p0266[1] missing.
Bit 30 = 1 (speed controller inhibited), if one of the following reasons is present:
- A 0 signal is available via binector input p0856.
- the function generator with current input is active.
- the measuring function "current controller reference frequency characteristic" is active.
- the pole position identification is active.
- motor data identification is active (only certain steps).
Bit 31 = 1 (enable signal missing), if:
- the speed setpoint from jog 1 or 2 is entered.
Description: Displays the actual status for the motor data identification (stationary measurement) and the speed/velocity controller
optimization (rotating measurement).
Value: 0: No measurement
115: Measurement q leakage inductance (part 2)
120: Speed controller optimization (vibration test)
140: Calculate speed controller setting
150: Measurement moment of inertia
170: Measurement magnetizing current and saturation characteristic
190: Speed encoder test
195: Measurement q leakage inductance (part 1)
200: Rotating measurement selected
210: Pole position identification selected
220: identification leakage inductance
230: Identification rotor time constant
240: Identification stator inductance
250: Identification stator inductance LQLD
270: Identification stator resistance
290: Identification valve lockout time
300: Stationary measurement selected
Note: Re r0047 = 300:
This value is also displayed if encoder calibration p1990 is selected.
Description: Displays the effective Motor Data Set (MDS) and the effective Encoder Data Sets (EDS).
Index: [0] = Motor Data Set MDS effective
[1] = Encoder 1 Encoder Data Set EDS effective
[2] = Encoder 2 Encoder Data Set EDS effective
[3] = Encoder 3 Encoder Data Set EDS effective
Dependency: Refer to: p0186, p0187, p0188, p0189, r0838
r0047 Motor data identification and speed controller optimization / MotID and n_opt
VECTOR_G Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 300 -
r0049[0...3] Motor data set/encoder data set effective / MDS/EDS effective
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8565
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals