SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
269
2 Parameters
2.2 List of parameters
Note: Re bits 00, 01, 02, 04, 05, 06, 09:
For PROFIdrive, these signals are used for status word 1.
Re bit 13:
When the "Safe Brake Control" (SBC) is activated and selected, the brake is no longer controlled using this signal.
Re bit 14, 15:
These signals are only of significance when the "extended brake control" function module is activated (r0108.14 = 1).
Description: Displays or sets the PROFIBUS address for PROFIBUS interface on the Control Unit.
The address can be set as follows:
1) Using the address switch on the Control Unit.
--> p0918 can then only be read and displays the selected address.
--> A change only becomes effective after a POWER ON.
2) Using p0918
--> Only if the address 00 hex, 7F hex, 80 hex, or FF hex has been set using the address switch.
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note: Permissible PROFIBUS addresses: 1 ... 126 (01 hex ... 7E hex)
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the send and receive telegram.
Value: 370: SIEMENS telegram 370, PZD-1/1
371: SIEMENS telegram 371, PZD-5/8
999: Free telegram configuration with BICO
Note: If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited.
The inhibited interconnections can only be changed again after setting value 999.
09 Control request Yes No -
11 Pulses enabled Yes No -
12 Open holding brake Yes No -
13 Command close holding brake Yes No -
14 Pulse enable from the brake control Yes No -
15 Setpoint enable from the brake control Yes No -
p0918 PROFIBUS address / PB address
CU_G130_DP,
CU_G150_DP
Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2401, 2410
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 126 126
p0922 IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
B_INF Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: 2401, 2420,
2423, 2447, 2457, 2481, 2483
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
370 999 999