2 Parameters
2.2 List of parameters
SINAMICS G130/G150
524 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2189 > p2190
Refer to: p2184, p2190
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2190 < p2189
Refer to: p2184, p2189
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the delay time to evaluate the load monitoring.
Description: Sets the torque threshold value for the message "Torque utilization < torque threshold value 2" (BO: r2199.11).
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency: Refer to: r0033, p2195, r2199
p2189[0...n] Load monitoring torque threshold 3 upper / M_thresh 3 upper
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Units group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]
p2190[0...n] Load monitoring torque threshold 3 lower / M_thresh 3 lower
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Units group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2192[0...n] Load monitoring delay time / Load monit t_del
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [s] 65.00 [s] 10.00 [s]
p2194[0...n] Torque threshold value 2 / M_thresh val 2
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 100.00 [%] 90.00 [%]