2 Parameters
2.2 List of parameters
SINAMICS G130/G150
704 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the operating mode of the circulating current control.
The circulating current control ensures symmetrical distribution of the total currents to the individual converters.
Value: 0: Circulating current control de-activated
1: Circulating current control activated
Dependency: Circulating current control is not possible for separate, offset motor winding systems (p7003 = 2).
Description: Sets the proportional gain for the circulating current controller.
The parameter is pre-set to the cable resistance.
Description: Sets the integral time of the circulating current controller.
The parameter is referred to the current controller sampling time (p0115[0]).
Dependency: Refer to: p0115
Description: Sets the limit of the circulating current controller output values.
The parameter is, depending on the phase, referred to the valve lockout times (p1828, p1829, p1830).
p7035[0...n] Par_circuit circulating current control operating mode / I_cct_ctrl mode
VECTOR_G (Parallel) Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 1
p7036[0...n] Par_circuit circulating current control proportional gain / Circ_I Kp
VECTOR_G (Parallel) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00000 [ohm] 200.00000 [ohm] 0.00000 [ohm]
p7037[0...n] Par_circuit circulating current control integral time / I_circ Tn
VECTOR_G (Parallel) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
2.0 1000.0 4.0
p7038[0...n] Par_circuit circulating current control limit / I_circ limit
VECTOR_G (Parallel) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 [%] 100 [%] 50 [%]

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals