2 Parameters
2.2 List of parameters
SINAMICS G130/G150
602 List Manual (LH2), 04/2014, A5E03263479A
Dependency: Refer to: r4022
Note: DI: Digital Input
Description: Displays the inverted status of the digital inputs of Terminal Module 31 (TM31).
Dependency: Refer to: r4022
Note: DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description: Sets the bidirectional digital inputs/outputs as input or output on the Terminal Module 31 (TM31).
Note: DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for digital output DO 0 (X481.5) of the Terminal Board 30 (TB30).
Note: DO: Digital Output
r4023.0...11 CO/BO: TM31 digital inputs status inverted / TM31 DI status inv
TM31 Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 9549, 9550,
9552, 9560, 9562
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X520.1) High Low -
01 DI 1 (X520.2) High Low -
02 DI 2 (X520.3) High Low -
03 DI 3 (X520.4) High Low -
04 DI 4 (X530.1) High Low -
05 DI 5 (X530.2) High Low -
06 DI 6 (X530.3) High Low -
07 DI 7 (X530.4) High Low -
08 DI/DO 8 (X541.2) High Low -
09 DI/DO 9 (X541.3) High Low -
10 DI/DO 10 (X541.4) High Low -
11 DI/DO 11 (X541.5) High Low -
p4028 TM31 set input or output / TM31 DI or DO
TM31 Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 9549, 9560,
9562
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 DI/DO 8 (X541.2) Output Input -
09 DI/DO 9 (X541.3) Output Input -
10 DI/DO 10 (X541.4) Output Input -
11 DI/DO 11 (X541.5) Output Input -
p4030 BI: TB30 signal source for terminal DO 0 / TB30ssDO0
TB30 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9099, 9102
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0