[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency: Refer to: r4120
Description: Displays the smoothing time constant for the temperature filter for Terminal Module 150 (TM150).
Dependency: Refer to: r4105, p4111, r4112, r4113
Note: The time constant lies in the range from 80 to 1000 ms and depends on the number of channels that are
simultaneously active.
Description: Sets the rated line frequency for the filter to skip the line frequency for Terminal Module 150 (TM150).
Value: 0: 50 Hz
1: 60 Hz
Description: Sets the sensor type of the first temperature sensor for the motor temperature monitoring.
Value: 0: No sensor
10: PTC fault
11: PTC alarm
12: PTC alarm & timer
20: KTY84
30: Bimetallic NC contact fault
31: Bimetallic NC contact alarm
32: Bimetallic NC contact alarm & timer
Dependency: Refer to: r0458, p0600, p0601
Note: This parameter is effective only when p0601 = 10.
PTC thermistor: Tripping resistance = 1650 Ohm
Information on using temperature sensors is provided in the following literature:
- hardware description of the appropriate components
- SINAMICS S120 Commissioning Manual
r4120 TM150 temperature filter time constant / TM150 temp_filt T
TM150 Can be changed: - Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: 9626, 9627
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [ms] - [ms] - [ms]
p4121 TM150 filter rated line frequency / TM150 filt f_line
TM150 Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: 9626, 9627
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p4600[0...n] Motor temperature sensor 1 sensor type / Temp_sens 1 type
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: EDS, p0140 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 32 0

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals